9000 SERIES
PHOTOELECTRIC TYPE SINGLE STATION/MULTI-STATION SMOKE
ALARMS/AC POWERED WITH BATTERY BACK-UP, 120VAC/9VDC,
60Hz OR 220VAC/9VDC, 50/60Hz
Installation Instructions - Owner's Information READ CAREFULLY AND SAVE
INTRODUCTION 9000 SERIES
HOW YOUR SMOKE ALARM WORKS
The 9000 Series smoke alarm operates on the photoelectric light
scatter principle. The unit's sensing chamber houses a light source
and a light sensor.
The 9123 & 9223 Series smoke alarm is a photoelectric type unit
for use as an evacuation device in residential and commercial
residential applications, while the 9120 & 9220 Series are for use as
an alert and relocate device. Each smoke alarm has a solid state
piezo signal to warn and alert the household to the presence of
threatening smoke.
The darkened sensing chamber is exposed to the atmosphere and
designed to permit optimum smoke entry from any direction while
rejecting light from outside the smoke alarm.
The light source is an infrared (invisible) LED which pulses every 8
seconds. The light sensor is a photodiode matched to the light
frequency of the LED light source.
Under normal conditions, the light generated by the pulsing infrared
LED is not seen by the light sensor, as it is positioned out of the direct
path of the light beam. When smoke enters the sensing chamber, light
from the pulsing LED light source is reflected by the smoke particles
onto the photodiode light sensor. At the first sighting of smoke, the
device is put into a pre-alarm mode.
This is indicated by a rapidly flashing LED on the face of the smoke
alarm. Once the light sensor confirms smoke for 2 consecutive pulses
inside the chamber, the light sensor produces the signal necessary to
trigger the alarm and sound the electronic horn.
This technique of verifying the smoke condition, combined with a
5-to-1 signal-to-noise ratio, substantially reduces the possibility of
nuisance alarms.
Your photoelectric smoke alarm is designed to detect the smoke
that results from an actual fire. Consequently, it is uncommon for
household smoke such as cigarette smoke or normal cooking smoke
to cause an alarm.
BASIC SAFETY INFORMATION
Dangers, Warnings, Cautions and Notices alert you to important
operating procedures or to potentially hazardous situations. Pay
special attention to these items.
WARNING!
ꢀ This photoelectric smoke alarm is listed for use in single-family and
multi-family residences, along with hotels, motels and other
commercial residential occupancies.
ꢀ This photoelectric smoke alarm must receive continuous 120VAC,
60Hz , pure sine wave electrical power. (battery is meant for
emergency back-up only). In order for the emergency battery back-up
to work, a new battery must be properly installed (see BATTERY
INSTALLATION section).
ꢀ NEVER ignore your smoke alarm if it sounds. Refer to IF YOUR
SMOKE ALARM SOUNDS section for more information. Failure to
do so can result in serious injury or death.
ꢀ Test this device once a week per manufacturer installation
recommendation. If the device ever fails to test correctly, replace
immediately! If the device is not working properly, it can not alert you
to a problem.
ꢀ This product is intended for use in indoor locations of family dwelling
units.
HOW TO TELL IF YOUR SMOKE ALARM IS
MODELS
WORKING PROPERLY
(SEE BACK OF SMOKE ALARM FOR EXACT MODEL)
ꢀ Your smoke alarm is provided with an alarm horn and pulsating
Light Emitting (indicator) Diode, which pulses every 30 seconds, and
a green AC power on LED.
ꢀ When turning the test knob on the smoke alarm to TEST 1 the red
light emitting diode should flash rapidly and the horn should sound.
ꢀ If the battery is low or missing, a chirp will be emitted when the red
LED flashes. If the smoke alarm is malfunctioning, the chirp will
sound between the red LED flashes. If AC power fails, the green
LED will turn off.
ꢀ The test knob of your smoke alarm simulates actual smoke
conditions.
NOTE: Tandem Interconnect Models.
ꢀ When testing one smoke alarm, the device that is activated will flash
the red indicator light and sound its alarm horn. All other units will
sound the alarm horn with their red indicator lights remaining off.
The relays will also activate on all units in tandem on models
equipped with the relay option.
*
9120. . . . . . . .. . . . . . . .. . . . . . . .. . . . . . . .. . . . . . 120VAC, 60Hz
** 9123. . . . . . . .. . . . . . . .. . .. . .120VAC, 60Hz with temporal 3 horn
9220. . . . . . . .. . . . . . . .. . . . . . . .. . . . . . . .. .. . .220VAC, 50/60Hz
** 9223. . . . . . . .. . . . . . . . . ..220VAC, 50/60Hz with temporal 3 horn
*
*
These units produce a non-temporal audible alarm and are therefore
not intended for locations where the desired action of the occupant(s)
is evacuation.
** Per NFPA 72, the American National Standard Audible Emergency
Evacuation Signal as defined in ANSI S3.41, is required whenever
the intended response is to evacuate the building.
OPTIONS, SELECTIONS:
T
- Integral 135°F Thermal Sensor
H - Isolated 135°F Thermal Sensor
- 1 Form A/1 Form C Auxiliary Relay
F
NOTICE: In the event AC Power fails, a 9VDC battery will provide
proper alarm operation for a minimum of 24 hours.
FIRE PROTECTION PLAN: WHAT YOU CAN DO TO
ELECTRICAL SPECIFICATIONS
MAKE YOUR FAMILY SAFE FROM FIRES
This smoke alarm can quickly alert you to the presence of smoke; it
cannot prevent fire. The ultimate responsibility for fire protection rests
solely on you.
OPERATING VOLTAGE. . . . . . . .. . . . . . . .. . . . . .. . . . 120VAC, 60Hz
OPERATING CURRENT (MAX.) (120VAC/9VDC). . . . . . . 0.070 amps
OPERATING VOLTAGE. . . . . . . .. .. . . . . . . .. . . . . .220VAC, 50/60Hz
OPERATING CURRENT (MAX.) (220VAC). . . . . . . . .. . . .0.046 amps
Installing smoke alarms is just the first step in protecting your family
from fires. You also must reduce the chances that fires will
O
O
OPERATING AMBIENT TEMPERATURE RANGE. .. . . . 40 F to 100 F
ALARM HORN RATING. . .. . . .. .. .meets or exceeds 85dBA at 10 feet
550-0093
Page 9-1
29.5.1.1 Where required by applicable laws, codes or standards for a
specific type of occupancy, approved single and multiple-station smoke
alarms shall be installed as follows:
Figure 3
1) In all sleeping rooms and guest rooms
2) Outside of each separate dwelling unit sleeping area, within 6.4m
(21ft) of any door to a sleeping room, the distance measured along a
path of travel
Figure 3: IN DWELLING UNITS WITH MORE THAN ONE
SLEEPING AREA, A SMOKE ALARM SHOULD BE PROVIDED TO
PROTECT EACH SLEEPING AREA IN ADDITION TO SMOKE
ALARMS REQUIRED IN BEDROOMS.
3) On every level of a dwelling unit, including basements
4) On every level of a residential board and care occupancy (small
facility), including basements and excluding crawl spaces and
unfinished attics
In addition to smoke alarms outside of the sleeping areas and in
each bedroom, NFPA 72 requires the installation of a smoke alarm on
each additional level of the dwelling unit, including the basement.
These installations are shown in Figure 4. The living area smoke
alarm should be installed in the living room or near the stairway to the
upper lever, or in both locations. The basement smoke alarm should
be installed in close proximity to the stairway leading to the floor
above. Where installed on an open-joisted ceiling, the smoke alarm
should be placed on the bottom of the joists. The smoke alarm should
be positioned relative to the stairway so as to intercept smoke coming
from a fire in the basement before the smoke enters the stairway.
5) In the living area(s) of a guest suite
6) In the living area(s) of a residential board and care occupancy
(small facility)
29.5.1.2 Where the area addressed in 29.5.1.1(2) is separated from
the adjacent living areas by a door, a smoke alarm shall be installed in
the area between the door and the sleeping room, and additional
alarms shall be installed on the living area side of the door as
specified by 29.5.1.1 and 29.5.1.3.
29.5.1.3 In addition to the requirements of 29.5.1.1(1) through
29.5.1.1(3), where the interior floor area for a given level of a dwelling
unit, excluding garage areas, is greater than 93m2 (1000ft2), smoke
alarms shall be installed per 29.5.1.3.1 and 29.5.1.3.2.
29.5.1.3.1 All points on the ceiling shall have a smoke alarm within a
distance of 9.1m (30ft) travel distance or shall have an equivalent of
one smoke alarm per 46.5m2 (500ft2) is evaluated by dividing the total
interior square footage of floor area per level by 46.5m2 (500ft2).
29.5.1.3.2 Where dwelling units include great rooms or vaulted/
cathedral ceilings extending over multiple floors, smoke alarms located
on the upper floor that are intended to protect the aforementioned area
shall be permitted to be considered as part of the lower floor(s)
protection scheme used to meet the requirements of 29.5.1.3.1.
The installation of additional alarms of smoke, heat or CO type
should result in a higher degree of protection. Adding alarms to rooms
that are normally closed off from the required alarms increases the
escape time because the fire does not need to build to the higher level
necessary to force smoke out of the closed room to the required
alarms. As a consequence, it is recommended that the householder
consider the installation of additional fire protection devices. However,
it should be understood that NFPA 72 does not require additional
smoke alarms over and above those called for in Figures 1, 2, 3 and 4
where required smoke alarms are shown.
Figure 4
Figure 4: A SMOKE ALARM SHOULD BE LOCATED ON EACH
LEVEL IN ADDITION TO EACH BEDROOM.
Are More Smoke Alarms Desirable? The required number of
smoke alarms might not provide reliable early warning protection for
those areas separated by a door from the areas protected by the
required smoke alarms. For this reason, the use of additional smoke
alarms for those areas for increased protection is recommended. The
additional areas include the basement, bedrooms, dining room, fur-
nace room, utility room, and hallways not protected by the required
smoke alarms. The installation of smoke alarms in kitchens, attics (fin-
ished or unfinished), or garages is not normally recommended,
because these locations occasionally experience conditions that can
result in improper operation.
Figure 1
IMPORTANT CONSIDERATION
NFPA 72, 2010 Edition, Chapter 29, Section 29.8.1.4(5)(b)
states: “Smoke alarms installed in one- and two-family dwellings
shall not remain in service longer than 10 years from the date of
manufacture.” Smoke alarms should be replaced for the
following reasons:
Figure 1: A SMOKE ALARM SHOULD BE LOCATED ON EVERY
LEVEL OF DWELLING UNIT, INCLUDING BASEMENT, WITHIN
EACH SLEEPING ROOM AND OUTSIDE SLEEPING AREAS.
ꢀ Dust, dirt, and other environmental contaminants can affect your
smoke alarm over a prolonged period.
Where to Locate the Required Smoke Alarms. The major threat
from fire in a dwelling unit occurs at night when everyone is asleep.
Persons in sleeping areas can be threatened by fires in the remainder
of the unit; therefore, smoke alarms are best located in each bedroom
and between the bedroom areas and the rest of the unit as shown in
Figure 2.
ꢀ Fast changing industry consensus standards and codes on all
smoke alarms make it advisable to periodically upgrade your
devices to maximize life safety.
ꢀ Assurance that your smoke alarm needs are kept abreast with the
constantly improving electronic technology.
ꢀ Smoke alarms are recognized as one of the lowest cost ways to
protect dwelling inhabitants against the danger of fire(s). It makes
good common sense to periodically replace and update your
smoke alarm that contributes so much to life safety.
Figure 2
MOUNTING LOCATION
This smoke alarm can be mounted on a ceiling or wall with equal
efficiency in either location.
ꢀ Ceiling location - smoke alarm should be mounted as close as
possible to the center of a hallway or room.
ꢀ Wall location - locate the top of the smoke alarm not more than 12
inches from the ceiling.
Figure 2: A SMOKE ALARM SHOULD BE LOCATED BETWEEN THE
SLEEPING AREA AND THE REST OF THE DWELLING UNIT AS
WELL AS IN EACH BEDROOM.
Figures 1, 2, 3, & 4 are reprinted with permission from NFPA 72, National Fire Alarm Code®,
Copyright ©2002, National Fire Protection Association, Quincy, MA 02169. This reprinted
material is not the complete and official position of the National Fire Protection Association on
the referenced subject which is represented only by the standard in its entirety. National Fire
Alarm Code® and NFPA 72® are registered trademarks of the National Fire Protection
In dwelling units with more than one bedroom area or with
bedrooms on more than one floor, more than one smoke alarm is
required, as shown in Figure 3.
Association, Inc., Quincy, MA 02169.
550-0093
Page 9-3
block openings to the sensing chamber and keep the device from
sensing smoke.
Figure 5
ꢀ Near fresh air inlets, returns or excessively drafty areas. Air
conditioners, heaters, fans, and fresh air intakes and returns can drive
smoke away from smoke alarms, making the devices less effective.
ꢀ In dead air spaces at the top of a peaked roof or in the corners
between ceilings and walls. Dead air may prevent smoke from
reaching a smoke alarm. See Figures 5 and 6 for recommended
mounting locations.
ꢀ In insect-infested areas. If insects enter a smoke alarm's sensing
chamber, they may cause a nuisance alarm. Get rid of the bugs
before installing smoke alarms where bugs are a problem.
ꢀ Near fluorescent light fixtures. Electrical "noise" from nearby
fluorescent light fixtures may cause a nuisance alarm. Install smoke
alarms and fluorescent lights on separate electrical circuits.
WARNING! Never disconnect an AC smoke alarm to silence a
nuisance alarm. Open a window or fan the air around the unit to
remove the smoke. The smoke alarm will automatically turn off when
the smoke in the air is completely gone. Do not stand close to the
unit. The sound produced by the device is loud because it is designed
to awaken you in an emergency. Prolonged exposure to the horn at a
close distance may be harmful to your hearing.
Figure 5: RECOMMENDED SMOKE ALARM MOUNTING
LOCATIONS
Figure 6
Figure 6: RECOMMENDED SMOKE ALARM LOCATION IN ROOMS
WITH SLOPED, GABLED, OR PEAKED CEILINGS.
The placement of the smoke alarm is critical if maximum speed of
fire detection is desired. Thus, a logical location for a smoke alarm is
the center of the ceiling. At this location, the device is closest to all
areas of the room.
INSTALLATION 9000 SERIES
CAUTION: New Construction: DO NOT attach smoke alarm head
until AFTER sanding, painting, and other dust creating situations are
finished and cleaned up.
WHERE SMOKE ALARMS SHOULD BE INSTALLED
WIRING/GENERAL
1. Use U.L. Listed cable with Class 1 insulation.
2. Observe local code requirements. Use box connector to anchor
cable to outlet box.
IN MOBILE HOMES
In mobile homes built after about 1978 that were designed and
insulated to be energy-efficient, smoke alarms should be installed as
described in the section above.
3. Metal outlet boxes must be grounded to earth ground.
4. NOTICE: Use only Duracell MN 1604 battery with the 9000
Series smoke alarms. Available at many retail stores.
CAUTION: Turn off electricity to prevent SHOCK and damage to
smoke alarm. Be sure the power line to the unit is not controlled by
any on/off switch, or other type of switch, other than a fuse or circuit
breaker.
IMPORTANT: Insure that all fluorescent lighting fixtures are properly
grounded.
NOTICE: Smoke alarm installation must conform to the electrical
codes in your area and to Article 760 of the U.S. National Electrical
Code. Wire installation should be performed only by a licensed
electrician.
In older mobile homes that have little or no insulation compared to
today's standards, uninsulated metal outside walls and roofs can
transfer heat and cold from outdoors, making the air right next to them
hotter or colder than the rest of the inside air. These layers of hotter or
colder air can prevent smoke from reaching a smoke alarm.
Therefore, install smoke alarms in such units only on inside walls not
more than 12 inches (30 cm) from the ceiling. If you are not sure
about the insulation level in your mobile home, or if you notice that the
walls or ceiling are unusually hot or cold, install the smoke alarm on an
inside wall.
Minimum protection requires one smoke alarm as close to the
sleeping area as possible. For better protection, install one smoke
alarm in each room, but first read the "Locations to Avoid."
MOUNTING OUTLET BOX
Use a 2" x 3" switch box or a 4" square or octagon junction box.
Mount a box for each smoke alarm. If wall mounting is desired, be
sure the box screws are oriented to upper right and lower left corners.
Be sure to use supplied Mounting Plate.
LOCATIONS TO AVOID
Nuisance alarms are caused by placing smoke alarms where they
will not operate properly. To avoid nuisance alarms, do not place
smoke alarms:
NOTE: For trouble areas where there can be a large volume of air
blowing out through the electrical junction box. You must first insert
the cardboard shield packaged with your smoke alarm to the backside
of device before securing it to the mounting plate.
ꢀ In or near areas where combustion particles are normally
present such as kitchens; in garages where there are particles of
combustion in vehicle exhausts; near furnaces, hot water heaters, or
gas space heaters. Install smoke alarms at least 20 feet (6 meters)
away from kitchens and other areas where combustion particles are
normally present.
WIRING ONE SMOKE ALARM
1. Run a minimum of 16 gauge, 2-conductor cable, plus ground
(3 wires) to the junction box from a power supply. Smoke alarms shall
be connected to their own dedicated circuit. Use ANSI/UL Listed
Class 1 wire.
ꢀ In air streams passing by kitchens. Figure 7 shows how a
smoke alarm can be exposed to combustion particles in normal air
movement paths, and how to correct this situation.
Figure 7
NOTE: The wiring to be used shall be in accordance with the
provisions of Article 300.3(b) of the National Electrical Code,
NFPA 70, as well as Article 210.
2. Make wire connections to the supplied plug-in connector as
follows: black to black, white to white, and connect the ground
wire to the metal outlet box.
ꢀ In damp or very humid areas, or next to bathrooms with showers.
The moisture in humid air can enter the sensing chamber as water
vapor, then cool and condense into droplets that cause a nuisance
alarm. Install smoke alarms at least 10 feet (3 meters) away from
bathrooms.
ꢀ In very cold or very hot environments, or in unheated buildings
or outdoor rooms, where the temperature can go below or above the
operating range of the smoke alarm. Temperature limits for proper
operation are 40° to 100°F (4.4° to 37.8°C).
ꢀ In very dusty or dirty areas. Dust and dirt can build up on the
smoke alarm's sensing chamber and can make it overly sensitive, or
NOTE/RED-YELLOW WIRE: The red-yellow wire from the smoke
alarm is for tandem connection only. DO NOT USE, AND DO NOT
REMOVE INSULATION CAP UNLESS CONNECTING ANOTHER
SMOKE ALARM.
550-0093
Page 9-4
Smoke Alarm Wiring Diagram
BATTERY INSTALLATION
1. Remove smoke alarm from mounting plate by turning counter-
clockwise.
BLK
1
11
10
7
HOT
CAUTION
POWER
WHT
NEUT
RED/YELLOW wire to be
capped when not in use.
This wire is for tandem
connection only. Do not
connect to any other circuit.
RED / YEL
TANDEM
2. Remove AC power connector and unsnap power leads from top of
the old battery. Snap new battery onto snaps and reinsert battery
through hole in back of smoke alarm. WARNING: Units with battery
back-up will not provide power or transmit an alarm to AC only units
in the event of an AC power failure. All battery back-up units in
tandem with good batteries will operate normally during an AC
power failure for a minimum of 24 hours.
VIO
ALARM
CONTACTS
VIO / BLK
6
BLU
ORN
3
9
ACCESSORY
ALARM
CONTACTS
YEL
4
2
BRN
RATED LOAD RESISTIVE
1.0 AMP @ 24VDC MAX
0.6 AMP @ 125VAC MAX
0.56 AMP @ 220VAC MAX
5
BRN
ISOLATED
THERMAL
GRAY
8
3. Use only Duracell MN 1604 battery with the 9000 Series smoke
alarms. Available at many retail stores.
GRAY
12
SMOKE
ALARM
PLUG
MOUNTING: PLATE & SMOKE ALARM
1. Lace the connector through the provided mounting plate and secure
the plate to the junction box.
WIRING TWO OR MORE SMOKE ALARMS
Tandem Installation
NOTICE: All smoke alarms in a tandem installation must be
controlled by the same fuse or circuit breaker. Otherwise tandem units
will not operate. Tandem will operate in the event of AC power failure if
battery is connected to the smoke alarm.
2. Plug the wire connector into the smoke alarm base.
LIMITATIONS: A maximum of 12 smoke alarms (9120/9123 or
9220/9223) may be connected together. Do not exceed 125 feet
between each smoke alarm. Do not exceed 1125 feet between first
and last smoke alarm.
NOTICE: A maximum of six (6) smoke alarms of either model
9120/9123 or 9220/9223 with the relay options (F, TF, HF) may be
tandem interconnected.
3. Place smoke alarm up to mounting plate, rotating it clockwise until
smoke alarm firmly snap locks into place. Keep smoke alarm
parallel to mounting plate so upper and lower tabs on plate seat
correctly into smoke alarm.
Wire used for interconnection shall be in accordance with article
760 of the latest edition of National Electrical Code (NFPA 70) and
must not exceed a resistance of 10 ohms.
QUICK DISCONNECT
START
FINISH
TYPE PLUG
LIMITATIONS
ELECTRICAL
BOX
VAC
SMOKE
Maximum of 12
ALARM
smoke alarms may be
connected together.
Do not exceed 125
feet between each
ELECTRICAL
BOX
smoke alarm. Do not
SMOKE
ALARM
exceed 1125 feet
WORK CONNECTOR WIRES BACK
THROUGH HOLE IN ADAPTER PLATE
ROTATE ALARM TO UPRIGHT
POSITION
between the first and
last smoke alarm.
CHECKOUT & TROUBLESHOOTING
TANDEM WIRE
TO ADDITIONAL
RED / YEL
1. Turn test knob to NORMAL position and install battery and then
supply house power to smoke alarm. The red indicator light should
flash every 15-30 seconds, showing smoke alarm is Operating
properly.
SMOKE ALARMS
NEUTRAL / WHITE
(MAX 12 ALARMS
HOT / BLACK
PER SYSTEM)
1. Run a minimum of 16 gauge, 3-conductor cable, plus ground (4
wires) to the first alarm junction box from a power supply and between
all smoke alarms that are to be connected together. Use ANSI/UL
Listed Class 1 wire. Power limited cable for multiple tandem
connections are available at many commercial electrical retail stores.
2. Make wire connections to the supplied plug-in connector as follows:
black to black, white to white, 3rd conductor to the red/yellow wire.
The red/yellow wire should be stripped to make the connection.
Connect ground wire between metal outlet boxes.
2. If red light is not flashing or the green LED is not on:
a. Check that the battery is installed.
b. Check the connector plug and wire connections. NOTE: Be sure you
turn off power before checking wire connections.
c. If power supply and wiring check out, but red light does not flash or
green LED is still off, return the smoke alarm to manufacturer. See
TO RETURN A SMOKE ALARM.
d. When powering up smoke alarms in a tandem installation and all
smoke alarms sound immediately, inspect all smoke alarms for
those with an illuminated indicator light. These will be the trouble
units.
3. Testing with Test Knob:
a. Rotate test knob counter-clockwise to TEST 1 position and wait up
to 20 seconds for smoke alarm to sound. If smoke alarm does not
sound after 20 seconds, return smoke alarm for service.
b. After successfully testing smoke alarm, return test knob to NORMAL
(non-test) position and wait 20 seconds for alarm to stop sounding.
NOTES ON TANDEM INTERCONNECTING MODELS
ꢀ DO NOT connect Gentex smoke alarms to other manufacturers'
smoke alarms.
ꢀ No more than 12 Gentex models 9120T, H/9123T, H or 9220T, H/
9223T, H may be connected in tandem.
ꢀ No more than 6 Gentex models 9120F, TF, HF/9123F, TF, HF or
9220F, TF, HF/9223F, TF, HF may be connected in tandem.
ꢀ All units connected in tandem MUST get their power from the same
circuit, that is, all smoke alarms in tandem must be controlled by the
same fuse or circuit breaker.
c. To test smoke alarm for high sensitivity, turn test knob clockwise to
TEST 2 position. Alarm should remain silent.
d. Make sure to return test knob back to its normal position.
e. If your smoke alarm sounds during this test it means the smoke
alarm's sensitivity has become too high and may cause false
alarms.
ꢀ After installation to verify proper working conditions all horns must
sound in this system.
NOTICE: If all interconnected alarms do not emit alarm signal during
commissioning test, refer to “WIRING TWO OR MORE SMOKE
ALARMS” section to insure alarm wiring is in accordance with tandem
wiring diagam.
CAUTION: Failure to observe any of the conditions set forth may
cause system malfunction and damage to the smoke alarm.
550-0093
Page 9-5
f. This could mean your smoke alarm is dirty and should be cleaned as
described in the maintenance procedure below.
IMPORTANT: IT IS RECOMMENDED TO CHANGE WASH AND
RINSE WATER AFTER FIVE (5) SMOKE ALARMS. IF YOUR
SMOKE ALARMS ARE EXTREMELY DIRTY, WATER SHOULD BE
CHANGED MORE FREQUENTLY.
NOTICE: SMOKE ALARMS ARE TO BE AIR DRIED ONLY. DO NOT
PLACE ALARM IN OVEN, MICROWAVE OR USE A HOT AIR
BLOWER TO ACCELERATE DRYING TIME. THIS COULD
RESULT IN DAMAGE TO YOUR SMOKE ALARM.
g. If the smoke alarm continues to alarm, for TEST 2 position following
cleaning, return it to Gentex for service.
h. To check for proper smoke entry into your smoke alarm's sensing
chamber, Gentex recommends using the Home Safeguard Smoke
Spray or CHEKKIT® SMOKE Detector Tester from SDI.
i. This test should be performed once a year and should be sprayed
from a distance no closer than 12 inches from the smoke alarm.
In the event you experience difficulty in the cleaning of your smoke
alarm or if you have any questions, please contact Gentex Corporation
or your local Gentex distributor.
MAINTENANCE
After your smoke alarm has been in operation for a period of time or
if it was installed prior to the completion of all building construction, your
device may have become more sensitive due to dirt build-up in the
smoke alarm's optic sensing chamber which could cause nuisance
alarms or could cause activation from small amounts of smoke build-up.
If this should occur, following this simple washing procedure will
restore your smoke alarm back to its original condition.
For further information, regarding frequency of cleaning and testing,
refer to NFPA 72, NFPA, Batterymarch Park, Quincy, MA 02269.
NOTICE: Failure to follow full cleaning instructions could result in
damage to this smoke alarm. DO NOT remove all smoke alarms at
the same time for cleaning.
If the smoke alarm does not work properly, do not try
and fix it yourself. This will void your warranty. See "To Return a
Smoke Alarm" for instructions to return smoke alarms that do not
operate properly. DO NOT TRY TO FIX IT YOURSELF.
IMPORTANT: Gentex recommends smoke alarms be tested a
minimum of once a week.
WARNING! Never use an open flame of any kind to test your smoke
alarm. You may ignite and damage the smoke alarm as well as your
home. The test feature of your smoke alarm accurately simulates
smoke conditions and tests the smoke alarm's functions as required by
ANSI/UL 217.
1. Turn off electrical power to the smoke alarm.
2. Rotate the smoke alarm counter-clockwise to remove it from its
mounting plate.
3. Unplug the connector from the back of the smoke alarm. Do not
remove the wire connection; leave the connector for your
replacement smoke alarm or jumper plug. Remove the battery.
4. Select three (3) standard size wash buckets and fill them each with
one gallon of normal tap water (distilled or de-ionized treated water
is recommended as a final rinse if water is extremely hard in
your area).
WARNING! Do not cover, tape, or otherwise block the openings of
your smoke alarm. These openings are designed to allow air to pass
through your smoke alarm, thus sampling the air around the smoke
alarm.
WARNING! Smoke alarms are not to be used with detector guards
unless the combination has been evaluated and found suitable
for that purpose.
FAILURE TO REGULARLY CLEAN THIS SMOKE ALARM WILL
RESULT IN FALSE ALARMS. A BUILD UP OF DUST CREATES AN
OBSCURATION THAT SIMULATES SMOKE. THIS MEANS THE
UNIT WILL GO INTO ALARM WITHOUT A FIRE CONDITION.
5. Add 1/8 cup of Ivory dishwashing liquid to the first bucket of water
and allow it to mix thoroughly, then place one dirty smoke alarm into
the soap water mixture until it becomes completely covered or
submerged. NOTE: If the smoke alarms are exceptionally dirty, you
may wish to first wipe off any excess dirt before washing unit so as
not to dirty the wash water too quickly.
DO NOT open smoke alarm for cleaning. IF SMOKE ALARM IS
OPENED DURING CLEANING, PRODUCT WARRANTY BECOMES
VOID.
TO RETURN A SMOKE ALARM
Should you experience problems with your smoke alarm, proceed
as follows:
1. Turn off electrical power to the smoke alarm.
2. Twist the smoke alarm counter-clockwise to remove it from its
mounting plate.
3. Unplug the connector from the back of the smoke alarm. Do not
remove the wire connection; leave the connector for your
replacement smoke alarm.
NOTICE: ONLY IVORY DISHWASHING LIQUID IS TO BE USED.
OTHER BRANDS ARE NOT RECOMMENDED AND MAY CAUSE
YOUR SMOKE ALARM TO MALFUNCTION.
4. Remove battery from smoke alarm. Do not ship smoke alarm with
battery still attached to battery clip.
5. Carefully pack (the manufacturer cannot be responsible for
consequential damage) and return to the manufacturer. Include
complete details as to exact nature of difficulties being experienced
and date of installation.
6. Return to: Gentex Corporation, 10985 Chicago Drive, Zeeland,
Michigan 49464. Prior to returning, call Gentex at 1-800-436-8391
or e-mail [email protected] to obtain a RMA Number from our
return department.
6. Allow smoke alarm to soak for approximately 10 minutes (longer
if extremely dirty). Then agitate for 5 or 10 seconds to flush out any
remaining dirt left inside smoke alarm's housing.
7. Remove smoke alarm from wash water and transfer directly to one of
the first rinse buckets containing clear water. Again, allow smoke
alarm to become completely submerged, agitate once more for 5 or
10 seconds to remove soap residue.
8. Finally, transfer smoke alarm to your second and final rinse bucket,
repeating method found in Step 7, then remove smoke alarm to a
clean dry area for a period of 48 hours to allow it to thoroughly dry.
LIMITED WARRANTY
For a period of 12 months from the date of purchase, or a maximum of 18 months from the date of manufacture,
Gentex warrants to you, the original consumer purchaser, that your Smoke Alarm will be free from defects in
workmanship, materials, and construction under normal use and service. If a defect in workmanship, materials,
or construction should cause your Smoke Alarm to become inoperable within the warranty period, Gentex will
repair your Smoke Alarm or furnish you with a new or rebuilt replacement Smoke Alarm without charge to you
except for postage required to return the Smoke Alarm to us. Your repaired or replacement Smoke Alarm will be
returned to you free of charge and it will be covered under this warranty for the balance of the warranty period.
This warranty is void if our inspection of your Smoke Alarm shows that the damage or failure was caused by
abuse, misuse, abnormal usage, faulty installation, improper maintenance, or repairs other than those performed
by us.
ANY WARRANTIES IMPLIED UNDER ANY STATE LAW, INCLUDING IMPLIED WARRANTIES OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, APPLY ONLY FOR THE WARRANTY
PERIOD SPECIFIED ABOVE. PLEASE NOTE THAT SOME STATES DO NOT ALLOW LIMITATIONS ON HOW
LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE EXCLUSION MAY NOT APPLY TO YOU.
GENTEX WILL NOT BE LIABLE FOR ANY LOSS, DAMAGE, INCIDENTAL OR CONSEQUENTIAL
DAMAGES OF ANY KIND ARISING IN CONNECTION WITH THE SALE, USE, OR REPAIR OF THIS SMOKE
ALARM. PLEASE NOTE THAT SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF
INCIDENTAL OR CONSEQUENTIAL DAMAGES. SO THE ABOVE EXCLUSION MAY NOT APPLY TO YOU.
If a defect in workmanship, materials, or construction should cause your Smoke Alarm to become
inoperable within the warranty period, you must return the Smoke Alarm to Gentex postage prepaid. You must
also pack the Smoke Alarm to minimize the risk of it being damaged in transit. You must also enclose a return
address. Smoke Alarms returned for warranty service should be sent to: Gentex Corporation, 10985 Chicago
Drive, Zeeland, MI 49464.
If we receive a Smoke Alarm in a damaged condition as the result of shipping, we will notify you and you
must file a claim with the Shipper.
THIS LIMITED WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER
RIGHTS WHICH VARY FROM STATE TO STATE.
Important Notice:
These materials have been prepared by Gentex Corporation ("Gentex") for informational purposes only, are necessarily summary, and are not purported to serve as legal advice and should not be used as such. Gentex makes no representations and warranties, express or implied, that these
materials are complete and accurate, up-to-date, or in compliance with all relevant local, state and federal laws, regulations and rules. The materials do not address all legal considerations as there is inevitable uncertainty regarding interpretation of laws, regulations and rules and the
application of such laws, regulations and rules to particular fact patterns. Each person's activities can differently affect the obligations that exist under applicable laws, regulations or rules. Therefore, these materials should be used only for informational purposes and should not be used as a
substitute for seeking professional legal advice. Gentex will not be responsible for any action or failure to act in reliance upon the information contained in this material.
GENTEX CORPORATION
10985 CHICAGO DRIVE, ZEELAND, MI 49464
PHONE: 1-800-436-8391
1-1-93
Pg. 9-6
550-0093-XAB
|