1.  
CB-Link Description  
The CB-Link driver allows the FieldServer to transfer data to and from devices over RS-485  
using CB-Link protocol. The information that follows describes how to expand upon the factory  
defaults provided in the configuration files included with the FieldServer.  
Refer to “Model 833-2771 CB-Link” Manual #65-0216 and “Model 833-2757 General Purpose  
Interface ControlBus Module” Manual #65-0220 from Cleaver Brooks.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
 
FS-8700-23 Cleaver Brooks Hawk Driver Manual  
Page 4 of 13  
2.  
Driver Scope of Supply  
2.1. Provided by FieldServer Technologies for this driver  
Fieldserver Technologies Part #  
Description  
RS-485 7-way connector adapter with attached  
cable  
SPA59137  
2.2.  
Provided by the Supplier of 3rd Party Equipment  
PART #  
DESCRIPTION  
CB-Link Controller  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
 
FS-8700-23 Cleaver Brooks Hawk Driver Manual  
Page 5 of 13  
3.  
Hardware Connections  
The FieldServer can be connected to the CB – Link device as shown below.  
Configure the PLC according to manufacturer’s instructions  
CLEAVER BROOKS MODEL 833-2771 CB LINK or  
HONEYW ELL Q7700 NETW ORK INTERFACE UNIT  
AKA: ASCII INTERFACE  
EMS INTERFACE  
BDI CARD  
QS7850  
GPI (GENERALPURPOSE INTERFACE)  
FURTHER CB-LINKS  
6
SLOT  
1
2
3
4
5
A
B
C
C1  
C2  
RS485  
9600 N81  
CONFIG PC  
(RUISYS)  
POSSIBLE DEVICES  
BCS7700  
CB-HAW K  
RM7800  
RM7800  
QS7X00X  
PULSATROL,  
BURNER CONTROL  
BURNER CONTROL  
BURNER CONTROL  
EXPANDED ANNUNCIATOR  
CARDS (QM40XX,  
MODEL 8051  
TRAPSCAN)  
Power  
Net  
1
Net  
2
P8  
P7  
P6  
P5  
P4  
P3  
P2  
P1  
Q7700  
NETW ORK INTERFACE.  
etc  
RS 232  
Ethernet  
10 Base T  
R2  
RS 485  
(Opto - Isolated)  
R1  
GROUND  
DTR  
RTS  
5
6
7
8
1
2
3
4
Rx  
CTS  
DSR  
8
1
Tx  
GROUND  
DC AUX Power  
SYSTEM NODE: 8  
CB  
HAW K  
R2  
RS 485  
(Opto - Isolated)  
R1  
(408)-262-2299  
FIELDSERVER - CLEAVER BROOKS  
CONNECTION DIAGRAM  
BASE NAME:  
FILE NAME: T28700-23.VSD  
DATE: 7/9/01  
BY: MN  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
 
FS-8700-23 Cleaver Brooks Hawk Driver Manual  
Page 6 of 13  
4.  
Configuring the FieldServer as a ChB-Link Client  
For a detailed discussion on FieldServer configuration, please refer to the FieldServer  
Configuration Manual. The information that follows describes how to expand upon the factory  
defaults provided in the configuration files included with the FieldServer (See “.csv” sample files  
provided with the FieldServer).  
This section documents and describes the parameters necessary for configuring the FieldServer  
to communicate with a ChB-Link Server  
Note that * indicates an optional parameter, with the bold legal value being the default.  
4.1.  
FieldServer  
Section Title  
Bridge  
Column Title  
Title  
Function  
Title for CSV file  
Node ID of the FieldServer  
Legal Values  
Any text, Maximum 32 characters  
8 – 254  
System_Node_ID  
Example  
// Common Information  
Bridge  
Title,  
CB_Link client,  
System_Node_ID  
11  
4.2.  
Data Arrays/Descriptors  
Section Title  
Data_Arrays  
Column Title  
Data_Array_Name  
Data_Format  
Function  
Provide name for Data Array  
Provides data format  
Legal Values  
Up to 15 alphanumeric characters  
INT16, INT32, BIT, FLOAT  
1-10,000  
Data_Array_Length Number of Data Objects  
Example  
// Data Arrays  
Data_Arrays  
Data_Array_Name,  
DA_AI_01,  
Data_Format,  
Float,  
Data_Array_Length  
200  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
 
FS-8700-23 Cleaver Brooks Hawk Driver Manual  
Page 7 of 13  
4.3.  
Client Side Connection Descriptions  
Section Title  
Connections  
Column Title  
Function  
Legal Values  
Specify which port the device is connected to the  
FieldServer  
Port  
R1-R2  
Baud  
Specify baud rate  
9600  
Parity  
Specify parity  
None  
IC_Timeout  
Squelch_Timer Squelch suppression time  
Poll_Delay  
Inter-Character Timeout  
>10.0 s  
>0.02 s  
0,55  
Minimum time between polls  
Example  
// Client Side Connections  
Connections  
Port,  
R2,  
Baud,  
9600,  
Parity,  
None,  
Ic_Timeout,  
10,  
Squelch_Timer,  
0.02,  
Poll_Delay  
0.6  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
 
FS-8700-23 Cleaver Brooks Hawk Driver Manual  
Page 8 of 13  
4.4.  
Client Side Node Descriptors  
Section Title  
Nodes  
Column Title Function  
Legal Values  
Node_Name  
Provide name for node  
Up to 32 alphanumeric characters  
See Section 4.4.1 A, B, and C  
below  
CB Link_ID  
Device address  
Protocol  
Port  
Specify protocol used  
Port connection  
CB_Link  
R1-R2  
Specify controller connected to CB-  
Link  
Node_Type  
See Section 4.4.2  
Example  
// Client Side Nodes  
Nodes  
Node_Name,  
CBH1,  
CBlink_ID,  
0 1 20,  
Protocol,  
CB_Link,  
Port,  
R2,  
Node_Type  
Hawk  
4.4.1.  
Node_ID  
Format for declaring node ID is A B C.  
A: 0 if only one CB-Link is attached, 8–254 if multiple CB-Links are attached, Default = 0  
B: Slot the device is attached to in the PC Link 1-5, default 1  
C: Device type (Declare Device Type Code):  
Device Description  
Auxenh  
Ec78xx  
Efenh  
Hawk  
Llenh  
Orenh  
Pulsa  
Q7700  
Device Type Code  
26  
32  
26  
20  
26  
26  
19  
1
Qm40xx  
Rm78xx  
S7800  
S7830  
Tdenh  
17  
32  
36  
34  
26  
99  
18  
Testcard  
Trapscan  
4.4.2.  
Node_Type  
Hawk, EC78XX. Others by request. (Refer to Device Information Table)  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
 
FS-8700-23 Cleaver Brooks Hawk Driver Manual  
Page 9 of 13  
4.5.  
4.5.1.  
Client Side Map Descriptors  
FieldServer Related Map Descriptor Parameters  
Column Title  
Function  
Name of this Map  
Descriptor. This Name  
refers to the variable in  
the related .bp2  
property file.  
Name of Data Array  
where data is to be  
stored in the  
Legal Values  
Any of the variable names in  
the related .bp2 property file.  
Map_Descriptor_Name  
Data_Array_Name  
One of the Data Array  
names from “Data Array”  
section above  
FieldServer  
Starting location in Data 0 to maximum specified in  
Data_Array_Offset  
Function  
Array  
“Data Array” section above  
Function of Client Map  
Descriptor  
RDBC  
4.5.2.  
Driver Related Map Descriptor Parameters  
Column Title  
Function  
Legal Values  
One of the node names  
specified in “Client Node  
Descriptor” above  
>1.0s  
Name of Node to fetch  
data from  
Node_Name  
Scan_Interval  
Specify poll rate  
4.5.3.  
Timing Parameters  
Column Title  
Timeout  
Function  
Specify maximum response time  
Legal Values  
>30.0s  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
 
FS-8700-23 Cleaver Brooks Hawk Driver Manual  
Page 10 of 13  
4.5.4.  
Map Descriptor Example  
// Client Side Map Descriptors  
Map_Descriptors  
Map_Descriptor_Name,  
Control_Source,  
Data_Array_Name,  
DA_AI_01,  
Data_Array_Offset,  
1,  
Function, Node_Name,  
Scan_Interval,  
10,  
Timeout  
30  
RDBC,  
CBH1,  
Oper_Pressure,  
DA_AI_01,  
2,  
RDBC,  
CBH1,  
10,  
30  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
 
FS-8700-23 Cleaver Brooks Hawk Driver Manual  
Page 11 of 13  
Appendix A. Advanced Properties  
Appendix A.1. Property Files  
Each Controller interfacing to the FieldServer requires associated property files (denoted by  
file extensions .bp1 and .bp2) to be loaded into the FieldServer. At present, the property  
files listed in the device information table below are preloaded onto the FieldServer when  
delivered. Other property files may be available upon request.  
Appendix A.2. Configuration Files  
Each Controller listed in the device information table below has an associated configuration  
file as shown in the device information table. This configuration file can be used as a basis  
for building a configuration for the FieldServer as it contains the mapping for the related  
module.  
Note: SYSNet is the generic name for networks of the following modules. Controlbus is the  
generic name for the networks in a NIM/CBLink configuration  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
 
FS-8700-23 Cleaver Brooks Hawk Driver Manual  
Page 12 of 13  
Appendix B. Device Information Table  
NETWORK INTERFACE UNIT  
MAKE  
MODEL  
Q7700  
NAME  
Network Interface Unit  
Honeywell  
Cleaver  
Brooks  
833-2771  
CB-Link  
CONTROL MODULES  
MODEL No.  
PROPERTY FILE  
NAME (.BP1;.BP2) NAME (.CSV)  
CONFIGURATION FILE  
MAKE  
OF  
MODULE NAME  
NOTES  
MODULE  
Honeywell QS7700A  
Honeywell QS7800A  
BCS7700  
7800 SERIES Control  
N/A  
N/A  
N/A  
N/A  
Data Acquisition  
Modules  
Honeywell QS7800C  
QM40XX Data Acquisition Module ON REQUEST  
QM40XX  
Armstrong QS7800D  
Honeywell QS7800E  
Trapscan System  
PulsaFeeder PULSAtrol  
ON REQUEST  
PULSA  
ON REQUEST  
PULSA  
Expanded  
Annunciator  
Honeywell QS7800A  
Honeywell QS7800A  
Honeywell QS7800A  
S7830 Expanded Annunciator  
S7800 Keyboard/Display Module  
ST7800 Relay Module  
S7830  
S7800  
ST7800  
S7830  
S7800  
Requires S7800  
module  
Honeywell  
Honeywell  
Honeywell  
RM7800E,G,L,M Relay Modules  
RM7840E,G,L,M Relay Modules  
Q7700A,B  
RM78XX  
RM78XX  
RM78XX  
RM78XX  
N/A∗  
CB-Link  
CB-Link  
CB-Link  
CB-Link  
CB-Link  
833-2727  
833-2729  
833-2734  
833-2734  
833-2734  
Display Module  
Data Control Bus Module  
CB 783  
CB 780  
CB 784  
N/A  
N/A  
ON REQUEST  
ON REQUEST  
ON REQUEST  
N/A  
N/A  
ON REQUEST  
ON REQUEST  
ON REQUEST  
Requires 833-2727 or  
833-2729 on module  
.
This is the chassis that the above modules plug into  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
 
FS-8700-23 Cleaver Brooks Hawk Driver Manual  
Page 13 of 13  
THIS PAGE INTENTIONALLY LEFT BLANK.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
 

EAW Stereo Amplifier CAM160 User Manual
Eiki Projector LC SVGA870U User Manual
Extron electronic Computer Hardware RGB 118 User Manual
FoodSaver Food Saver V2860 1 User Manual
Fostex Music Pedal FE 204 User Manual
FujiFilm Digital Camera Z1000EXR User Manual
Fundex Games Board Games 2612 User Manual
GE Convection Oven PK916BM User Manual
GE Monogram Clothes Dryer PSXH43 User Manual
GE Oven PGS968 User Manual